3 Phase UPS - Big Transformerless 3 Phase Online UPS Power 10K-80kva
1:High Frequency Online UPS Transformerless, 3 (Three) Phase, 380/400/415Vac In/Out
2:UPS apply for Industry, Bank, Hospital, School, Hospital, Telecom etc use
3: Twin-channel line for UPS input:
4: UPS power factor is as high as 0.99
5: :UPS with N+X parallel redundancy
Key Specifications/Special Features:
Applications: servers, data-center, critical network devices, sensitive electronic equipment, and telecommunication
Product specification:
1:Product rating: 10 to 80kVA
2:Voltage: 305 to 477V AC without battery use
3:Frequency: 40 to 70Hz
4:Power factor: 0.8 or 0.9
5: Phase: 3 phase input and 3 phase output
Features:
1:N+X parallel redundancy
The maximum of the inbuilt parallel mode is 8 UPS without any other external accessories and compatible to battery share in the parallel mode
2:High-efficient DSP chip:
The digital Ti DPS controlling chip provides precise data processing capability with excellent performance in output and reliability
3:Outstanding electric property:
The efficiency of the machines is as high as 93% and reaches over 98% in the ECO mode, the input power factor is as high as 0.99
4:Twin-channel line input:
The UPS provides customer security in power supply with intelligent choice between two-line input or one-line input according to the actual condition
5: Intelligent management of battery charging and discharging
Payment Details:
Payment Terms: T/T
Minimum Order: 10-99 Units
Delivery Details:
FOB Port: Shenzhen
Lead Time: 5 - 15 days
Product Certificate: CE
Technical Specification
Product Series
|
ES33 10-80KVA
|
Model
|
ES3310K
|
ES3315K
|
ES3320K
|
ES3330K
|
ES3340K
|
HP3360K
|
HP3380K
|
Capacity (VA/W)
|
10KVA/8KW
|
15KVA/12KW
|
20KVA/16KW
|
30KVA/24KW
|
40KVA/32KW
|
60KVA/48KW
|
80KVA/64KW
|
Rectifier Input
|
RectifierType
|
IGBT-based Vector Controlled PFC(PF Corrected)
|
Input Voltage
|
380/400/415VAC(Accepted from 305 to 477 without battery use)
|
Input Frequency
|
50HZ or 60HZ(Accepted range from 40 to 70)
|
Input Current THD
|
<3%(without any Filter)
|
Input Power Factor
|
≥0.99(without any Filter)
|
Power Walk-In
|
5 to 30s (selectable)
|
Bypass Input
|
Input Voltage
|
380/400/415VAC
|
Battery
|
Battery Type
|
VRLA(Valve Regulated Lead Acid) or Wet/Flooded or NiCd
|
End-Cell Voltage
|
1.60-1.90VDC (for VRLA)
|
DC Ripple Current(float)
|
<5%(of DC10 AH capacity )RMS value
|
DC Ripple Voltage(float &const V Ch)
|
<1% (RMS value)
|
Temp.Comp.
Charge
|
Standard(where internal batteries 10,15,20,30Kva) and Optional(for all other battery configurations)
|
Output
|
Inverter Type
|
IGBT-based Vector,Repetitive&PI Controlled
|
Output Voltage
|
380/400/415VAC±5 Regulation (3-phase RMS average)
|
Output Frequency
|
50/60HZ(±0.05)
|
Output Voltage THD
|
1%( max)
|
Max.Load Crest Factor
|
3:1(compliant with IEC62040-3)
|
Transient Volt.Resp
|
10ms to recover ±0.5 of Nominal Voltage for 0% to 100% or 100% to 0% step load
|
Max.Leading PF Load
|
Up to 0.9
|
Voltage Displacement
|
120º±10º(with 100% unbalanced load)
|
Overload
|
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute.
|
Efficiency
|
AC-AC
|
Up to 96%
|
EMC-Class
|
Class-A(Applicable for both Radiated &Conducted)
|
Environmental
|
Storage Temp.
|
-20-70 Centigrade (UPS)&-20-30 Centigrade (Battery)
|
Operating Temp
|
0-40 Centigrade (UPS)&25±5 Centigrade (Battery)
|
Relative Humidity
|
0-95%(non-condensing)
|
Maximun Altitude above Mean Sea Level
|
1000m(as per IEC 62040/3)
|
Main unit
|
Dimension(W*D*H)mm
|
420*643*956
|
420*643*956
|
420*643*956
|
470*710*1150
|
470*710*1150
|
673*835*1550
|
673*835*1550
|
Wight(KG)
|
115
|
117
|
122
|
160
|
164
|
450
|
510
|
UPS Enclosure IP
|
IP20ï¼ÂÂeven with open front doorï¼ÂÂ
|